In manufacturing environments, QC laboratories play a vital role in ensuring product quality and safety. Adherence to laboratory guidelines and standards is crucial for maintaining data integrity, regulatory compliance, and operational efficiency. This article offers an in-depth look at essential laboratory standards and guidelines tailored for QC lab managers and technicians.
Laboratory Chemical Hoods
Usage
- ANSI/ASSP Z9.5-2022: Ensure adequate laboratory chemical hoods or other engineering controls to prevent employee overexposure to air contaminants generated by laboratory activities.
- US OSHA 29 CFR Part 1910.1450: Adequate ventilation is critical. Ensure each lab worker has access to 2.5 linear feet of hood space if they work primarily with chemicals.
- NFPA 45-2000: Avoid using canopy hoods, biological safety cabinets, and laminar flow cabinets in place of laboratory hoods to ensure proper containment and safety.
Sash-Closers
ANSI/ASSP Z9.5-2022: Use automatic sash positioning systems with obstruction sensing to avoid injuries and spills. Emphasize the importance of closed sash operation in work procedures.
Location
- SEFA 1.2-2002: Balance laboratory fume hood exhaust systems with room exhaust systems for necessary ventilation and fume control during non-working hours.
- NFPA 45-2000: Place laboratory hoods in areas with minimal air turbulence and away from high-traffic areas to prevent disruption due to air currents.
- ASHRAE 1995 HVAC Applications Handbook: Consider air supply distribution patterns, researcher movements, and external factors like open windows and doors to maintain fume hood effectiveness.
Face Velocity
- ANSI/ASSP Z9.5-2022: Maintain average face velocities in the range of 80-100 fpm to capture and contain hazardous emissions effectively. Lower velocities may suffice for hoods with excellent containment characteristics.
- NFPA 45-2000: Ensure laboratory hood face velocities and exhaust volumes are sufficient to contain contaminants and protect personnel.
- SEFA 1.2-2002: Establish face velocities based on the toxicity or hazard of materials used. A target average face velocity is typically around 100 FPM.
- US OSHA 29 CFR Part 1910.1450: Keep hood face velocities typically in the range of 60-100 lfm to avoid excessive turbulence.
Flow Monitoring and Alarms
Face Velocity Monitors
- ANSI/ASSP Z9.5-2022: Equip all hoods with flow indicators or alarms to alert users to improper exhaust flow. Calibrate these devices annually and ensure they provide visible and audible warnings for deviations.
- NFPA 45-2000: Ensure each laboratory hood has a measuring device for continuous indication of adequate airflow.
- SEFA 1.2-2002: Use monitors to indicate face velocity or exhaust flow verification for all hoods.
- US OSHA 29 CFR Part 1910.1450: Provide continuous monitoring devices for each hood to confirm performance before use.
Sash Alarms
ANSI/ASSP Z9.5-2022: Implement sash alarms and other mechanisms to ensure fume hoods function correctly and provide necessary protection.
Flow Visualization Testing
ANSI/ASSP Z9.5-2022: Conduct airflow visualization tests as per ANSI/ASHRAE 110-2016 to verify no visible escape beyond the sash plane.
Testing and Maintenance
Face Velocity Testing
ANSI/ASSP Z9.5-2022: Follow ANSI/ASHRAE 110 standards for testing fume hood face velocity and ensure compliance with design specifications.
Competing Air Flow TestingANSI/ASSP Z9.5-2022: Measure cross-draft velocities near hood openings to detect potentially interfering room air currents.
VAV Response Time Testing
ANSI/ASSP Z9.5-2022: Ensure Variable Air Volume (VAV) systems respond within 5 seconds to changes in sash position or operating modes.
Containment Testing
ANSI/ASSP Z9.5-2022: Conduct tracer gas containment tests during commissioning to ensure fume hoods provide adequate containment.
Frequency of Testing
- ANSI/ASSP Z9.5-2022: Perform routine performance tests at least annually or whenever significant changes occur in the hood system.
- NFPA 45-2000: Inspect and test laboratory hoods and exhaust systems annually and correct deficiencies immediately.
Special Hoods and Conditions
Perchloric Acid Hoods
ANSI/ASSP Z9.5-2022: Use specially designed hoods for handling perchloric acid to avoid explosive conditions and ensure daily washdowns of the exhaust system.
Radioisotope Hoods
ANSI/ASSP Z9.5-2022: Avoid manifolding radioisotope hoods with non-radioisotope hoods unless appropriate filtration systems are in place.
Ductless Hoods
ANSI/ASSP Z9.5-2022: Ensure ductless hoods meet specific requirements and undergo hazard evaluation and analysis to maintain safety.
Chemical Laboratories
Ventilation Rates
- ANSI/ASSP Z9.5-2022: Establish minimum room ventilation rates to ensure effective dilution and removal of airborne hazards.
- NFPA 45-2000: Maintain continuous ventilation in laboratories, with at least four air changes per hour when unoccupied and more than eight when occupied.
- SEFA 1.2-2002: Typically, laboratories require four to twelve air changes per hour to maintain safe ventilation levels.
Room Pressure Differential
- ANSI/ASSP Z9.5-2022: Ensure airflow generally moves from low to high hazard areas to prevent contaminant spread.
- NFPA 45-2000: Maintain negative pressure in laboratory work areas relative to corridors and non-laboratory areas.
- ASHRAE 1995 HVAC Applications Handbook: Maintain appropriate pressure differentials in laboratory spaces to act as secondary confinement barriers.